Filipino Engineer

  • Increase font size
  • Default font size
  • Decrease font size

Breaking News

Earth Fault-Loop Impedance Part 3

E-mail Print PDF

In Part 2, we did a simple calculation for the maximum length of the cable. We have not considered the internal impedance of the source, i.e. the transformer impedance. Likewise, we just consider the current rating of the circuit breaker without the current multiplier for instantaneous tripping. The primary reason for that is to make the calculation much simpler. If I will tell everything all at once, understanding the concept may be difficult.

Circuit breakers are classified into three (3) according to their mean tripping current. We are dealing with IEC standards here and its derivative standards, ie BS, AS, etc.and not the IEEE.

Ia (typical values) for circuit breakers are as follows:
Type B = 4 x rated current
Range : 3In - 5In
Type C = 7.5 x rated current
Range : 5In - 10In
Type D = 12.5 x rated current
Range : 10In - 20In

From above formula, a Type B, 6A circuit breaker will have an instantaneous tripping current of 24A. The question may be raised, what is the circuit breaker type I need to use for my application / design. The answer is, it all depends on the application or design. for lighting and other domestic application, Type B is preferred. In normal application, Type C is normally used. For motor loads particularly where the motor starts loaded, then Type D is being used.

 

Earth Fault-Loop Impedance Part 2

E-mail Print PDF

As mentioned in Part 1, the value of the fault loop impedance shall be able to generate enough fault current to activate any protective device.

What does this mean? The earth fault current must be high enough to trigger the automatic disconnection of a protective device within an specified time. If the value of the earth fault current is not within the tripping current of the protective device, then there will be no means of protective device will provide protection against touch voltage. At the location of the fault, there is a possibility that the full voltage is present in the equipment enclosure posing hazard to people with the increased touch voltage higher than 50 Vac.

If in cases where there is no way to increase the fault current, say the distance of the fault from the supply is too far - cable impedance is limiting the earth fault current, the only solution will be using a residual current (earth leakage) protection. It is not always advisable to have this solution though. There are applications that when a residual current protection is used, annoying erratic device operation is possible particularly when the protection device setting is not correct.

In the event that a reduction of the earth fault-loop impedance required to ensure correct disconnection times of the protective device is not possible due to distance factor, additional bonding to earthing system may be used.

 

Earth Fault-Loop Impedance Part 1

E-mail Print PDF

What is "Earth Fault-Loop Impedance"? Why is it important?

Standards define "Earth Fault-Loop Impedance" as the impedance of the earth fault-current loop (active-to-earth loop) starting and ending at the point-of-earth fault.

It is important to know the earth fault-loop impedance of a circuit to ensure that during the occurence of a phase-to-earth fault, normally an insulation fault, the magnitude of the fault current is enough to cause the operation of the protective device within the required time particularly where the touch potential exceeds 50V a.c. or 120V ripple-free d.c.

The earth fault-loop in a MEN system comprises the following parts:

  1. The active conductor as far as the point of the fault, including supply mains service line, consumers mains, submains (if any) and the final subcircuit.
  2. The protective earthing conductor (PE), including the main earthing terminal/connection or bar and MEN connection.
  3. The neutral-return path, consisting of the neutral conductor (N) between the main neutral terminal or bar and the neutral point at the transformer, including supply mains, service line and consumers mains.
  4. The path through the neutral point of the transformer and the transformer winding
 
  • «
  •  Start 
  •  Prev 
  •  1 
  •  2 
  •  3 
  •  4 
  •  5 
  •  6 
  •  7 
  •  8 
  •  9 
  •  10 
  •  Next 
  •  End 
  • »


Page 1 of 10

Our Ads

Our Sponsors

Design Stages

Successful projects were not developed overnight. They have undergone through several stages. Missing any one stage may have caused disastrous effect on the projects causing failure.

Conceptual Design
To develop your project ideas into a more tangible perspective.
Front End Engineering and Design (FEED)
To explore possibilities to enable better control on the outcome of ideas, getting the final result without delay but more importantly without overshooting your budget.
All ideas need to be developed at this stage of the project.
Detail Design
The final stage of the design aspect of your project. Only minor, unforeseen and uncontrollable by the project team need to be implemented at this stage.
Injecting radical changes at this stage could mean redevelopment of the project concepts leading to project delays and budget overshoot.

We could offer the Electrical Engineering aspect of your project ideas. If you want to seek our help, contact us at HELP@FILIPINOENGINEER.


Statistics

Members : 175
Content : 62
Web Links : 7
Content View Hits : 28915
New Members:
  • Renata
  • Roomma
  • valeriaspinoza
  • skIpsyEpics
  • amateurteens

Spammers:

DeviceRadamir
deviceradamir@mail.ru
2009-01-06 06:58:32
schoooler
schoooler@gmail.com
2009-01-02 16:06:45
IvanPoddubniy
corkconry@gmail.com
2009-01-01 02:16:24
AssolBRT
assolbrt@gmail.com
2008-12-30 07:27:01
OnekRamma
ownerouttrurb@gmail.com
2008-12-29 15:49:37
PafInvatt
olfdfdvbb3@gawab.com
2008-12-26 19:12:52
kitesurftrips
kite_surf@mail.ru
2008-12-26 07:22:08
KigeReokSeemPek
maxbizmax-fax@yahoo.co.uk
2008-12-25 16:57:35
NickelbackK
nickelback00ei@gmail.com
2008-12-25 15:46:50
MileniaMcAdams
mileniamcad@mail.ru
2008-12-25 06:08:08

Due to the increase in spam registration, new users should validate their registration to be removed from the Spammers List Thank you!

Tag Cloud

atmosphere   cable   calculation   chapter   circuit   electrical   equipment   explosive   factor   fault   flammable   impedance   into   lightning   load   normal   protection   release   requirements   safety   source   standard   standards   systems   used   voltage  

Created with AkoCloud.

Who's Online

We have 8 guests online

Mission

To provide a knowledge base and tools for Filipinos to prepare them with the demands of the global job market.